APPLICATION:
LC1-D series AC contactor is suitable for using in the circuits
up to the rated voltage 660V AC 50Hz ro 60Hz,rated current 95A,for
making,breaking,frequent starting & controlling the AC motor.Combined
with the auxiliary contact block,air delayer & machine-interlocking
deviceetc,it becomes the delay contactor,mecxhanical interlocking
cintacor, stardelta starter.With the thermal relay,it is combined
into the electromagnetic starter. The Contactor is produced
according to IEC158-1,VDE0660 & BS5452. |
 |
Coil voltage(V) |
24 |
42 |
48 |
110 |
120 |
127 |
220 |
240 |
Frequeney(Hz) |
50 |
B5 |
D5 |
E5 |
F5 |
- |
G5 |
M5 |
U5 |
50/60 |
B7 |
D7 |
E7 |
F7 |
- |
G7 |
M7 |
U7 |
Coil voltage(V) |
380 |
415 |
440 |
480 |
500 |
600 |
660 |
Frequency(Hz) |
50 |
Q5 |
N5 |
R5 |
- |
S5 |
- |
Y5 |
50/60 |
Q7 |
N7 |
R7 |
- |
- |
- |
- |
|
SPECIFICATIONS:
Type |
LC1-D09 |
LC1-D12 |
LC1-D18 |
LC1-D25 |
LC1-D32 |
LC1-D40 |
LC1-D50 |
LC1-D65 |
LC1-D80 |
LC1-D95 |
Rated working current(A) |
AC3 |
9 |
12 |
18 |
25 |
32 |
40 |
50 |
65 |
80 |
95 |
AC4 |
3.5 |
5 |
7.7 |
8.5 |
12 |
18.5 |
24 |
28 |
37 |
44 |
AC3 capacity of phase 3 squirrel-cage motor
AC3(KW) |
220V |
2.2 |
3 |
4 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
25 |
380V |
4 |
5.5 |
7.5 |
11 |
15 |
18.5 |
22 |
30 |
37 |
45 |
415V |
4 |
5.5 |
9 |
11 |
15 |
22 |
25 |
37 |
45 |
45 |
440V |
4 |
5.5 |
9 |
11 |
15 |
22 |
30 |
37 |
45 |
45 |
660V |
5.5 |
7.5 |
10 |
15 |
18.5 |
30 |
33 |
37 |
45 |
45 |
Rated heat current(A) |
20 |
20 |
32 |
40 |
50 |
60 |
80 |
80 |
125 |
125 |
Electrical life |
AC4×104 |
20 |
20-15 |
20-7 |
15-7 |
15-7 |
10-7 |
7 |
7-6 |
7-5 |
7-5 |
AC3×106 |
2 |
2 |
2 |
2 |
2 |
2 |
2 |
1.6 |
1.6 |
1.6 |
Mechanical life×106 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
20 |
10 |
10 |
Number of the contact |
3P+NO |
3p+NC+NO |
3P+NC |
|
|
 |
|